Ansul Autopulse IQ-636X-2
The AUTOPULSE IQ-636X-2 Agent Releasing Control Panel is designed with modularity and easy system planning. The AUTOPULSE IQ-636X-2 can be configured with just a few devices for small building applications or for a large campus or high-rise application. Simply add additional peripheral equipment to suit the application.
request information »- AUTOPULSE IQ-636X-2 Kit Contains:
- (1) 434953 AUTOPULSE IQ-636X-2 CPU
- (1) 433614 Black Display Dress Panel-2 CP-DISP2
- (1) 433613 KDM-R2
- (2) 432794 Black Module Dress Plate BMP-1
- (1) 433526 CAB A4R Red
- (1) 433522 CAB A4R Door, Lock and Keys – Red
- (1) 434955 Battery Dress Plate BP2-4
- Certified for seismic applications when used with the appropriate seismic mounting kit
- Approved for Marine applications when used with listed compatible equipment
- One, expandable to two, isolated intelligent Signaling Line Circuit (SLC) Style 4, 6 or 7
- Up to 159 detectors (any mix of ion, photo, thermal, or multi-sensor) and 159 modules (NO manual stations, two-wire smoke, notification, or relay) per SLC. 318 devices per loop/636 total
- A 2x40 character display or optional 16x40 character display
- Four Notification Appliance Circuits (NAC) providing 1.5 Amps each with built-in Class A/B wiring options. Selectable System Sensor, Wheelock, or Gentex strobe synchronization
- Built-in Alarm, Trouble, and Supervisory relays
- VeriFire® Tools online or offline programming utility. Upload/Download, save, store, check, compare, and simulate panel databases. Upgrade panel firmware
- Autoprogramming and Walk Test reports
- Optional universal 636-point DACT
- Up to 32 remote annunciators can be added on EIA-485 bus
- EIA-485 annunciators, including custom graphics
- EIA-232 port for printing or PC connection
- History file with 800-event capacity in nonvolatile memory, plus separate 200-event alarm-only file
- Alarm Verification selection per point, with tally
- Positive Alarm Sequence (PAS) presignal
- Silence inhibit and Auto Silence timer options
- March time/temporal/California two-stage coding/strobe synchronization
- Field-programmable on panel or on PC, with VeriFire Tools program check, compare, simulate
- Full QWERTY keypad
- Charger for up to 18-200 amp hours of standby power
- Non-alarm points for lower priority functions
- Remote ACK/Signal Silence/System Reset/Drill via monitor modules
- Automatic time control functions, with holiday exceptions
- Extensive, built-in transient protection
- Powerful Boolean logic equations
- USB port for PC connection
- These listings and approvals apply to the basic AUTOPULSE IQ-636X-2 control panel. In some cases, certain modules may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status. The AUTOPULSE IQ-636X-2 complies with UL Standards 864, 9th Edition (Fire). It is designed to meet NFPA 72 Local, Auxiliary, Remote Station, and Proprietary (not applicable for FM) Fire System Requirements
- UL Listed S4935
- ULC Listed S4935
- FM Approved
- MEA 128-07-E
- California State Fire Marshall 7165-0595:117
- FDNY COA#6043
- OSHPD - .OSP-0072-10
- City of Chicago
- City and County of Denver
- CCCF Listed
- When used with the MARINE-EQ, appropriate seismic bracket, and marine approved devices, these agent releasing control panels are approved by the following agencies
- US Coast Guard 161.002/A50/0 (Standard 46 CFR)