The NFS-320 intelligent Fire Alarm Control Panel is part of the ONYX Series of Fire Alarm Controls from NOTIFIER. In stand-alone or network configurations, ONYX Series products meet virtually every application requirement. The NFS-320’s modular design makes system planning easier. The panel can be configured with just a few devices for small building applications, or networked with many devices to protect a large campus or a high-rise office block. Simply add additional peripheral equipment to suit the application. Wireless fire protection can be added with the SWIFT wireless gateway and devices.

request information »
  • NFS-320 Product Data
  • One isolated intelligent Signaling Line Circuit (SLC) Style 4, 6 or 7
  • Up to 159 detectors and 159 modules per SLC; 318 devices maximum
    • Detectors can be any mix of ion, photo, thermal, or multi-sensor; wireless detectors are available for use with the FWSG.
    • Modules include addressable pull stations, normally open contact devices, two-wire smoke detectors, notification, or relay; wireless modules are available for use with the FWSG.
  • Optional FWSG Wireless SWIFT Gateway supports wireless SLC devices
  • Standard 80-character display
  • Network options:
    • High-speed network for up to 200 nodes (NFS2-3030, NFS2-640, NFS-320(C), NFS-320SYS, NCA-2, DVC-EM, ONYX-Works, NFS-3030, NFS-640, and NCA).
    • Standard network for up to 103 nodes (NFS2-3030, NFS2-640, NFS-320(C), NFS-320SYS, NCA-2, DVC-EM, ONYX-Works, NCS, NFS-3030, NFS-640, NCA, AFP-200, AFP-300/400, AFP-1010, and AM2020). Up to 54 nodes when DVC-EM is used in network paging.
  • 6.0 A power supply with four Class A/B built-in Notification Appliance Circuits (NAC). Selectable System Sensor, Wheelock, or Gentex strobe synchronization
  • Built-in Alarm, Trouble, Security, and Supervisory relays
  • VeriFire Tools online or offline programming utility. Upload/Download, save, store, check, compare, and simulate panel databases. Upgrade panel firmware
  • Auto programming and Walk Test reports
  • Multiple central station communication options:
    • Standard UDACT
    • Internet
    • Internet/GSM
  • 80-character remote annunciators (up to 32)
  • EIA-485 annunciators, including custom graphics
  • Printer interface (80-column and 40-column printers)
  • History file with 800-event capacity in nonvolatile memory, plus separate 200-event alarm-only file
  • Alarm Verification selection per point, with automatic counter
  • Pre signal/Positive Alarm Sequence (PAS)
  • Silence inhibit and Auto Silence timer options
  • NAC coding functions:
    • March time
    • Temporal
    • California two-stage coding
    • Canadian two-stage
    • Strobe synchronization
  • Field-programmable on panel or on PC with VeriFire Tools program check, compare, simulate
  • Full QWERTY keypad
  • Battery charger supports 18 – 200 AH batteries
  • Non-alarm points for lower priority functions
  • Remote ACK/Signal Silence/System Reset/Drill via monitor modules
  • Automatic time control functions, with holiday exceptions
  • Extensive, built-in transient protection
  • Powerful Boolean logic equations
  • Approvals:
    • UL 864 (Fire)
    • UL 1076 (Burglary)
    • UL 2572 (Mass Notification Systems)
    • ULC-S527-11 Standard for the installation of Fire Alarm Systems
    • UL/ULC: S635
    • FM approved
    • CSFM:  7165-0028:0243
    • MEA: 128-07-E 
    • ULC Listed: S527-11
    • US Coast Guard: 161.002/50/0, 161.002/55/0 (Standard 46 CFR and 161.002)

ul-listed-logo.jpg  fm-appoved-logo.jpg

You may also be interested in...

recent news

Jun 12,2024

Kidde Natura Clean Agent Fire Suppression Systems

Kidde Natura Clean Agent Fire Suppression System...Read More »

Jul 5,2023

Why you should consider hiring Suppression Systems, Inc

Why you should consider hiring Suppression Systems, Inc...Read More »

questions? like to schedule a consultation?

Contact us!
person