Ansul Autopulse Z-10 Release Control Panel

Dedicated for Agent release: AUTOPULSE Z-10 suppression release panels provide conventional fire alarm control circuits and are equipped with the features required for a wide variety of single or dual hazard suppression release applications. Capabilities include automatic extinguishing agent release, and deluge and preaction sprinkler control. 

Flexible I/O capabilities: Four IDCs allow for either four separately monitored zones or two cross-zoned connections. Two SPMs allow dedicated manual inputs for release or abort. Two releasing appliance circuits (RACs) supervise the actuator coils and activate the actuators when required. The two NACs and the three panel auxiliary relays provide status condition information.

Easy program selections: The operator panel has a program mode that allows selection of panel operation type and detailed operating selections using an easily selected sequential programming operation.

History Log: The last 50 events are stored in non-volatile memory. This information is accessed by connecting a technician’s computer to the service port which is also used to set the date and time.

request information »

Ansul Z-10 Conventional Agent Release Control Panel Product Data

Agent Release Control Panel designed specifically for suppression release operation with:

  • Four initiating device circuits (IDCs)
  • Two notification appliance circuits (NACs)
  • Two release appliance circuits (rACs)
  • Two special purpose monitor inputs (SPMs) for manual release request and manual abort request
  • Three auxiliary relays with selectable functions 
  • Easily selected activity timing options

Agent release operation includes:

  • Automatic extinguishing release
  • Deluge and preaction sprinkler system release
  • Dual or single hazard area protection
  • Combined agent release and preaction operation
  • IDCs are selectable for cross-zoning or for activation from a single detection input 
  • Short circuit RAC supervision

Operator interface provides:

  • Status LEDs per circuit for Alarm, Trouble, and Supervisory (where appropriate)
  • Acknowledge, alarm silence, and system reset
  • Operating mode and timer selection when in programming mode

Audible Escalation of Events:

  • Single audible appliance tone:
    • Stage 1 activates Temporal or 20 bpm March Time pattern
    • Stage 2 activates 120 bpm March Time pattern to indicate release timer active
    • Release activates on steady to indicate release timer expired and actuator is activated
  • Dual audible appliance control (Single hazard):
    • RAC 2 provides a third NAC for dedicated Stage 1 bell control
    • NACs 1 & 2 indicate release as On Steady

Compatible with Listed/Approved 24 VDC coil automatic water control valves

Required system components:

  • Coil supervision module (Part No. 430687), one per solenoid control RAC
  • Maintenance Switch (Part No. 433936 or 433937), one per solenoid control RAC 

Approvals:

  • UL Listed: S4935
  • FM Approved: J.I.3012391
  • CSFM: 7165-0595:113
  • MEA (NyC): 49-03-E

fm-appoved-logo.jpg  ul-listed-logo.jpg

You may also be interested in...

recent news

Jul 5,2023

Why you should consider hiring Suppression Systems, Inc

Why you should consider hiring Suppression Systems, Inc...Read More »

Jun 22,2023

Lithium-Ion Batteries

Lithium-Ion Batteries...Read More »

questions? like to schedule a consultation?

Contact us!
person