Ansul Autopulse 542 Conventional Panels

The AUTOPULSE 542 is a six-zone Releasing Control Panel for single and dual hazard applications. The AUTOPULSE 542 provides reliable fire detection, signaling and protection for commercial, industrial and institutional buildings. The AUTOPULSE 542 is compatible with System Sensor’s i3 detectors which are conventional smoke detectors that can transmit a maintenance trouble signal to the panel indicating the need for cleaning and a supervisory ‘freeze’ signal when the ambient temperature falls below the detector rating of approximately 45 °F (7 °C). In addition, the control panel is compatible with conventional input devices such as two-wire smoke detectors, four-wire smoke detectors, pull stations, waterflow devices, tamper switches and other normally-open contact devices. Refer to Device Compatibility Document for a complete listing of compatible devices.

Four outputs are programmable as NACs (Notification Appliance Circuits) or releasing circuits. Three programmable Form-C relays (factory programmed for Alarm, Trouble and Supervisory) and 24 VDC special application resettable and non-resettable power outputs are also included on the main circuit board. The AUTOPULSE 542 supervises all wiring, AC voltage, battery charger and battery level.

Activation of a compatible smoke detector or any normally-open fire alarm initiating device will activate audible and visual signaling devices, illuminate an indicator, display alarm information on the panel’s LCD, sound the piezo sounder at the panel, activate the panel alarm relay and operate an optional module used to notify a remote station or initiate an auxiliary control function.

The AUTOPULSE 542(E) releasing panel offers the same features as the AUTOPULSE 542 but allows connection to 220/240 VAC. Unless otherwise specified, the information in this data sheet applies to both the 110/120 VAC and 220/240 VAC versions of the panels.

request information »
  • Autopulse 542R product data
    • ​Designed for CLEAN AGENT RELEASE standards NFPA 12, 12A, 12B and 2001
  • Autopulse 542D product data
    • Designed for FIRE SPRINKLER RELEASE standards NFPA 13, 15 and 16
  • Features:
    • Disable/Enable control per input zone and output zonen
    • Extensive transient protection
    • Dual hazard operation
    • Manual release/Abort combination zonen
    • Adjustable pre-discharge, discharge and waterflow delay timers
    • Cross-zone (double-interlock) capability
    • Six programmable Style B (Class B) IDCs (Initiating Device Circuit)
    • System Sensor i3 series detector compatible
    • Four programmable Style Y (Class B) output circuits – (special application power)
  • Strobe synchronization:
    • System Sensor
    • Wheelock
    • Gentex
    • Faraday
    • Amseco
  • Three programmable Form-C relays
  • Latching option for relays
  • Pre-discharge relay option
  • 7.0 amps total 24 VDC output current
  • Resettable and non-resettable output power
  • Built-in Programmer
  • Short circuit RAC supervision
  • ANN-BUS for connection to optional devices (up to eight total of any of the following):
    • ANN-80 Remote LCD Annunciator
    • ANN-I/O LED Driver
    • ANN-S/PG Printer Module
    • ANN-RLY Relay Module
    • ANN-LED Annunciator Module
  • 80-character LCD display (backlit)
  • Real-time clock/calendar with daylight savings time control
  • History log with 256 event storage
  • Piezo sounder for alarm, trouble and supervisory
  • 24 volt operation
  • Low AC voltage sense
  • Outputs programmable for:
    • Releasing Circuits
  • NACs programmable for:
    • Silence Inhibit
    • Auto-Silence
    • Strobe Synchronization
    • Selective Silence (horn-strobe mute)
    • Temporal or Steady Signal
    • Silenceable or Non-silenceable
    • Release Stage Sounder
    • Stage Silenceable Option
    • Cross Zone Pre-discharge
    • Cross Zone Discharge
  • Automatic battery charger with charger supervision
  • Optional Dress Panel DP-51050 (red)
  • Optional Trim Ring TR-CE (red) for semi-flush cabinet mounting
  • Optional CAC-5X Class A Converter Module for Outputs and IDCs
  • Optional 4XTM-F Municipal Box Transmitter Module
  • Optional Digital Alarm Communicators (411, 411UD, 411UDAC)
  • PROGRAMMING AND SOFTWARE:
    • Custom English labels (per point) may be manually entered or selected from an internal library file
    • Programmable Abort operation
    • Three programmable Form-C relay outputs
    • Eleven pre-programmed templates and one user-defined template
    • Continuous fire protection during online programming at the front panel
    • Program Check automatically catches common errors not linked to any zone or input point
    • Selectable timer options for Discharge 1 and 2, and Pre-discharge 1 and 2
  • USER INTERFACE:
    • Integral 80-character LCD display with backlighting
    • Real-time clock/calendar with automatic daylight savings adjustments
    • ANN-Bus for connection to remote annunciators
    • Audible or silent walk test capabilities
    • Piezo sounder for alarm, trouble, and supervisory
  • Approvals
    •  UL: S4935n
    • FM: Approvedn
    • CSFM: 7165-0595:118n
    • MEA: 333-07-E

fm-appoved-logo.jpg  ul-listed-logo.jpg

You may also be interested in...

recent news

Jul 5,2023

Why you should consider hiring Suppression Systems, Inc

Why you should consider hiring Suppression Systems, Inc...Read More »

Jun 22,2023

Lithium-Ion Batteries

Lithium-Ion Batteries...Read More »

questions? like to schedule a consultation?

Contact us!
person